EasyManuals Logo
Home>Siemens>Protection Device>SIPROTEC 7UT613 series

Siemens SIPROTEC 7UT613 series User Manual

Siemens SIPROTEC 7UT613 series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #217 background imageLoading...
Page #217 background image
2.8 Unbalanced Load Protection
217
7UT613/63x Manual
C53000-G1176-C160-2
In example, figure 2-97, the permanently permissible asymmetrical load amounts to
11 % of the machine internal current and the K-factor K = 20. As the relevant measur-
ing location for asymmetrical load is usually assigned to the side of the machine to be
protected, the setting can be effected directly under address 4034 FACTOR K:
FACTOR K = 20.
Figure 2-97 Example of a pre-defined asymmetrical load diagram
If, however, the asymmetrical load protection must be set in amps secondary during
operation, also the K-factor must be converted as it refers to the machine internal cur-
rent. The following applies:
Example:
Machine I
N
= 483 A
I
2perm
= 11 % (salient-pole machine)
K-factor = 20 s
Current transformer 500 A/5 A
results in the setting value under address 4034 FACTOR K:
The setting value 4035 T COOL DOWN is defined as the time required by the protected
object to cool down from 100 % to 0 % during prior stress with permissible asymmet-
rical load I2>. If the machine manufacturer does not provide this information, the
setting value can be calculated by assuming an equal value for cool-down time and

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals