1 Introduction
24
7UT613/63x Manual
C53000-G1176-C160-2
Busbar Protection 1-phase differential protection for a busbar with up to 9 or 12 feeders (depending
on the version)
Either one relay per phase or one relay connected via interposed summation
current transformers
Tripping characteristic with current restraint
Short tripping time
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
Monitoring of the current connections with operation currents.
Earth Fault Differ-
ential Protection
Earth fault protection for earthed transformer windings, generators, motors, shunt
reactors, or starpoint formers
Short command duration
High sensitivity for earth faults within the protected zone
High stability against external earth faults using the magnitude and phase relation-
ship of through-flowing earth current.
2 earth-fault differential protection functions possible
High-impedance
Unit Protection
Highly sensitive fault current detection using a common (external) burden resistor
Short tripping time
Insensitive against DC components and current transformer saturation
High stability with optimum matching
Suitable for earth fault detection on earthed generators, motors, shunt reactors, and
transformers, including auto-transformers, with or without earthed starpoint.
Suitable for any voltage measurement (via the resistor current) for application of
high-impedance unit protection
Tank Leakage Pro-
tection
For transformers or reactors the tank of which is installed isolated or with high re-
sistance
Monitoring of the current flowing between the tank and ground
Can be connected via a „normal“ current input of the device or the special highly
sensitive current input (3 mA smallest setting).
Time Overcurrent
Protection for
Phase Currents and
Residual Current
Two definite time delayed overcurrent stages for each of the phase currents and the
residual (threefold zero sequence) current, can be assigned to any of the sides of
the protected object or to any measuring point
Additionally, one inverse time delayed overcurrent stage for each of the phase cur-
rents and the residual current
Selection of various inverse time characteristics of different standards is possible,
alternatively a user defined characteristic can be specified
The stages can be combined as desired, different characteristics can be selected
for phase currents on the one hand and the residual current on the other
External blocking facility for any stage (e.g. for reverse interlocking)