1.3 Characteristics
27
7UT613/63x Manual
C53000-G1176-C160-2
Frequency Protec-
tion (devices with
measured voltage
inputs)
• Three underfrequency stages and one overfrequency stage
• Frequency measurement via the positive sequence component of the voltages
• Insensitive to harmonics and abrupt phase angle changes
• Adjustable undervoltage threshold
Circuit Breaker
Failure Protection
• With monitoring of current flow through each breaker pole on any side of the pro-
tected object
• Supervision of the breaker position possible (if breaker auxiliary contacts or feed-
back signal available)
• Initiation by each of the internal protection functions
• Start by external trip functions possible
• Single-stage or two-stage
• Short dropout and overshoot times
• 2 breaker failure protection functions are possible
External Direct Trip • Tripping of either circuit breaker by an external device via binary inputs
• Inclusion of external commands into the internal processing of information and trip
commands
• With or without trip time delay
• 2 breaker failure protection functions possible
Processing of ex-
ternal information
• Inclusion of external signals (user defined information) in internal information pro-
cessing
• Pre-defined transformer annunciations for Buchholz protection and oil gassing
• Transmission to output relays, LEDs, and via serial system interfaces to central
control and data storage facilities
Flexible Functions • Up to 12 individually configurable protection or monitoring functions
• Input quantities can be selected from all the connected 3-phase or 1-phase mea-
sured quantities
• Also possible from the measured or combined input quantities: symmetrical compo-
nents, power components, frequency
• Standard logic with supervision of the input quantities to over/undershooting of an
adjustable limit value
• Settable time and dropout delay
• External blocking via „Blocking on Measured Quantities Failure“ parameterisable
• Editable message texts
• Additional determination and output of up to 20 mean values from measured quan-
tities or calculated values
• Additional determination and output of up to 20 mean values from measured quan-
tities or calculated values

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals