1.3 Characteristics
27
7UT613/63x Manual
C53000-G1176-C160-2
Frequency Protec-
tion (devices with
measured voltage
inputs)
Three underfrequency stages and one overfrequency stage
Frequency measurement via the positive sequence component of the voltages
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold
Circuit Breaker
Failure Protection
With monitoring of current flow through each breaker pole on any side of the pro-
tected object
Supervision of the breaker position possible (if breaker auxiliary contacts or feed-
back signal available)
Initiation by each of the internal protection functions
Start by external trip functions possible
Single-stage or two-stage
Short dropout and overshoot times
2 breaker failure protection functions are possible
External Direct Trip Tripping of either circuit breaker by an external device via binary inputs
Inclusion of external commands into the internal processing of information and trip
commands
With or without trip time delay
2 breaker failure protection functions possible
Processing of ex-
ternal information
Inclusion of external signals (user defined information) in internal information pro-
cessing
Pre-defined transformer annunciations for Buchholz protection and oil gassing
Transmission to output relays, LEDs, and via serial system interfaces to central
control and data storage facilities
Flexible Functions Up to 12 individually configurable protection or monitoring functions
Input quantities can be selected from all the connected 3-phase or 1-phase mea-
sured quantities
Also possible from the measured or combined input quantities: symmetrical compo-
nents, power components, frequency
Standard logic with supervision of the input quantities to over/undershooting of an
adjustable limit value
Settable time and dropout delay
External blocking via „Blocking on Measured Quantities Failure“ parameterisable
Editable message texts
Additional determination and output of up to 20 mean values from measured quan-
tities or calculated values
Additional determination and output of up to 20 mean values from measured quan-
tities or calculated values