Device Functions
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
6-11
6.3 Stopping Modes 
Different stopping functions can be selected thanks to the large numbers of 
applications for which the SIRIUS 3RW44 soft starter can be used. The motor 
stop can be set optimally according to application and deployment. 
If a start command is output while the motor is being stopped, this process is 
aborted and the motor is started up again using the specified starting mode.
Note 
If guided stopping is selected as stopping mode (soft stop, pump stop or 
braking), it may be necessary to select a larger dimensioned branch (soft starter, 
wiring, branch protection elements and motor), since the current exceeds the 
motor rated current while the motor is being stopped. 
Figure 6-6:Stopping modes in general
6.3.1 Coasting Down 
Coasting down means that when the on command to the soft starter is removed, 
the energy feed to the motor via the soft starter is interrupted. The motor will 
coast down freely, only driven by the mass reactance (centrifugal mass) of the 
rotor and the load. This is designated as a natural run-down. A larger centrifugal 
mass means a longer coasting-down.
Typical applications for coasting down
Coasting down is used for loads with no special requirements in terms of 
stopping behavior, e.g. large fans.
4_7_Auslaufarten_allgemein.wmf
1
2
3
1
2
3
Motor
speed
     n
n
e
Stop command
at soft starter
n
Coasting down
n
Torque-controlled
stopping mode
n
DC braking
Time (t)
     s