Commissioning
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
5-11
5.4.2 Entering the Motor Data
Figure 5-6:Entering the motor data and name plate
Rated operating
current I
e
Notice
Always set the rated operating current of the motor stated on the motor name plate for the
prevailing supply voltage. This setting is independent of the connection method of the soft
starter (soft starter in standard or inside delta circuit). Value to be set in the above
example for a supply voltage of 400 V, e.g. 40.5 A.
The motor current of the connected drive should be set to ensure proper functioning of the
soft starter during starting and stopping as well as in regard to motor protection.
select
ESC
ESC OK
ESC OK
ESC OK
change
ESC OK
Motor 1
1
Rated operating
current Ie
1
change
Rated operating
torque
2
change
Rated operating
speed
3
OK
Function call
40.5 A
143 Nm
1470
Copy motor data
to PS2+3
Adjustable
from ... to
0 ... I
e
(3RW44 device
name plate)
0 ... 10,000 Nm
500 ... 3,600 min
-1
select
ESC
Parameter
1
set 1
select
ESC
Settings
3
OK
Display mea-
SIEMENS
Menu
3RW44
1
sured value
ESC
ESC OK
OK
select
1
Status display
select
2
ESC OK
OK
OK
OK
ESC OK
OK
Copy motor data
to PS2+3
execute?