EasyManua.ls Logo

Siemens SIRIUS 3RW44 - Activating the PROFIBUS DP Communication Module (Field Bus Interface) and Setting the; Introduction

Siemens SIRIUS 3RW44
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROFIBUS DP Communication Module
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
8-9
8.4 Activating the PROFIBUS DP Communication Module (Field
Bus Interface) and Setting the Station Address
8.4.1 Introduction
Activate the PROFIBUS DP communication module (device function "Field bus")
and set the station address either via the display or via the device interface using
the "Soft Starter ES Professional" or the "Soft Starter ES smart + SP1" software.
Notice
After activating the communication module, the control priority automatically
switches from the inputs to the
PROFIBUS DP communication module.
If an input is active with the "Manual operation local" function, the control priority
does not change (refer to Chapter 5.4.7 "Parameterizing the Inputs" on Page 5-
28).
The station address of the soft starters is pre-set to 126 as factory default.

Table of Contents

Other manuals for Siemens SIRIUS 3RW44

Related product manuals