Circuit Examples
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
9-7
9.1.6 3RW44 in a Standard Circuit and Control as per Contactor
Note 
With this circuit type, the motor start may be delayed by up to 5 s after the start command is issued due to 
the internal run times of the soft starter. Coasting down is the only possible stopping mode.
Notice 
After switching off the control supply voltage and before restarting, the device 
must be allowed to cool down for at least 30 s, as this influences the 
effectiveness of the inherent protection of the soft starter. 
This type of circuit is not recommended for higher switching frequencies as the 
integrated fan cannot idle after the soft starter has been switched off, thus 
reducing the switching frequency specified in the technical data.
1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12.
 Control circuit  Main circuit
$
1
3(
3(