EasyManua.ls Logo

Siemens SIRIUS 3RW44 - Data Sets 131, 141, 151 - Technology Parameters 2: Reading;Writing Set 1, 2, 3

Siemens SIRIUS 3RW44
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROFIBUS DP Communication Module
SIRIUS 3RW44 System Manual
8-62 GWA 4NEB 535 2195-02 DS 04
8.12.15 Data Sets 131, 141, 151 - Technology Parameters 2: Reading/Writing Set 1, 2, 3
Byte
Bit
Value Comment
Preamble
0 Coordination Writing 0x20 via channel C1 (PLC)
Writing 0x30 via channel C2 (PC)
Writing 0x40 via device interface (PC)
1 - 3 Reserved = 0
ID
No
.
Byte
Bit
Meaning
Only
for
data
set
131
Value range [coding] Factor
120 4 - 7 Device function_2 x
1 8 - 11 Device function_1 x
130 12 Rated operating current I
e
0 ... 2000 A [0 ... 200000] 0.01 A
316
0
Load type x 3-phase [0]
416
1
Protection against voltage failure x No [0]
•Yes [1]
16
2-7
Reserved = 0
136 17 Prewarning motor temperature x 0 ... 95 % [0 ... 19] 5 %
518
0-2
Response to overload - thermal motor model x Tripping without restart [0]
Tripping with restart [1]
Warning [2]
18
3-7
Reserved = 0
619
0-4
Tripping class x CLASS 5 (10a) [3]
CLASS 10 [0]
CLASS 15 [4]
CLASS 20 [1]
CLASS 30 [2]
CLASS OFF [15]
19
5-7
Reserved = 0
7 20 Pre-charge time x 60 ... 1 800 s [2 ... 60] 30 s
8 21 Idle time x 0 ... 255 s [0 ... 255] 1 s
137 22-23 Prewarning limit - tripping reserve x 0 ... 500 s [0 ... 500] 1 s
10 24
0-1
Response to overload - temperature sensor x Tripping without
restart [0]
Tripping with restart [1]
Warning [2]
24
2-3
Reserved = 0
924
4-6
Temperature sensor x Deactivated [0]
Thermoclick [1]
PTC - type A [2]

Table of Contents

Other manuals for Siemens SIRIUS 3RW44

Related product manuals