Commissioning
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
5-41
5.5 Other Device Functions
5.5.1 Measurement-value Display
Figure 5-32:Measurement-value display
Note
The "Phase currents" display always shows the currents in the supply
cable. That is, if the soft starter is operated in the "Inside delta circuit"
circuit type, the currents measured internally by the soft starter are
extrapolated to the supply cable current (phase current) by a factor of 1.73
and displayed.
Due to asymmetries, the phase currents in the inside delta circuit may
deviate from the currents running through the supply cables.
Note
When using the 3RW44 soft starter in an IT system with ground fault
monitoring: 3RW44, product version
*E06* and the PROFIBUS DP
communication module may not be used in this network configuration.
3RW44 soft starters as of product version *E07* can be used in
combination with the PROFIBUS DP communication module. However,
the phase voltage values (UL-N) and phase-to-phase voltage values (UL-
L) may be displayed incorrectly on the measurement-value display of the
3RW44.
select
ESC
Phase
1
select
ESC
Display mea-
1
OK
select
ESC
Phase-to-pha-
2
OK
select
ESC
Blocking
3
OK
select
ESC
Phase
4
OK
default
ESC
Power
5
OK
voltages
se voltages
voltages
0 W
sured value
default
ESC
Line frequency
6
OK
0 Hz
default
ESC
Supply voltage
7
OK
230 V
default
ESC
Heatsink
8
OK
22 °C
temperature
default
ESC
Motor heat
9
OK
0 %
build-up
default
ESC
Remaining time
10
OK
65540 s
for tripping
OK
ESC
Function call
Switch off
standard display
accept
ESC
Switch off
standard display
execute ?
ESC
OK
OK
OK
OK
OK
OK
OK
OK
SIEMENS
Menu
3RW44