Commissioning
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
5-43
5.5.3 Motor Control (Assigning Control Priority)
Figure 5-34:Motor control
Notice
The "Standard control" menu item specifies which control device should be the master
control device when the control supply voltage is applied.
When activating the PROFIBUS communication module, the setting is changed to
"Automatic/none".
Control device priority
Only a higher-priority control device can assume and hand over the control
priority (0 = lowest).
- 0: Automatic operation (input control through PLC via PROFIBUS)
- 1: PC via PROFIBUS (Soft Starter ES professional software required)
- 2: Inputs
- 3: Via display keys
- 4: PC via serial interface (Soft Starter ES professional software required)
Possible values
Activate key control?
Deactivate key control?
Execute control functions
Activate "Control inputs"?
Deactivate "Control inputs"?
Automatic / none
Inputs
Keys
select
ESC
Motor control
1
select
ESC
Motor
4
OK
select
ESC
Control motor
2
OK
change
ESC
Standard
3
OK
via inputs
control
Inputs
via keys
control
select
ESC
Settings
3
Display mea-