PROFIBUS DP Communication Module
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
8-11
The next step is to set the desired station address of the 3RW44 as PROFIBUS
slave.
In this example, the station address is set to "23".
Notice
If the parameter "Parameters disabled CPU/Master" is set to "Off" (factory setting), the
parameters set on the soft starter will be overwritten with the values stored in the GSD
data or in the OM when the bus is started. If this is not desired, the parameter must be set
to "On".
Baud rate
5
12,000 kBd
Substitute
select
6
select
Parameters dis-
select
7
change
Off
abled CPU/Master
Fieldbus
select
1
change
interface
On
ESC OK
Group diagnosis
select
2
change
Disable
ESC OK
Behavior on
change
3
Sw. subst. value
ESC OK
CPU/master-stop
Station address
select
accept
23
Station address
select
4
change
23
ESC OK
ESC
OK
Station address
select
accept
126
ESC OK
Station address
select
4
change
126
ESC
OK
Adjustable
from ... to
1... 126
Parameterization options
On, Off
Disable, enable
Substitute value, last value
ESC OK
ESC OK
ESC OK
value