PROFIBUS DP Communication Module
SIRIUS 3RW44 System Manual
8-24 GWA 4NEB 535 2195-02 DS 04
Table
The following table contains process data and process images:
Table 8-7: Process data and process images
Process data
Process image:
(16 O, DO 0.0 to DO 1.7)
(16 I, DI 0.0 to DI 1.7)
Outputs
DO- 0. 0 Motor right
1 Motor left
2 Available
3 Trip reset
4 Emergency start
5 Available
6 Slow speed
7 Available
DO- 1. 0 Output 1
1Output 2
2 Parameter set Bit 0
3 Parameter set Bit 1
4 Available
5 Available
6 Available
7 Disable quick stop
Inputs
DI- 0. 0 Ready (automatic)
1 Motor on
2 Group error
3 Group warning
4 Input 1
5 Input 2
6 Input 3
7 Input 4
DI- 1. 0 Motor current I
act-bit0
1 Motor current I
act-bit1
2 Motor current I
act-bit2
3 Motor current I
act-bit3
4 Motor current I
act-bit4
5 Motor current I
act-bit5
6 Manual operation local operating mode
7 Ramp operation