PROFIBUS DP Communication Module
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
8-65
163 96 Output 1 - Action x • No action (default) [0]
• Control source PAA-DO 1.0
output 1 [1]
• Control source PAA-DO 1.1
output 2 [2]
• Control source input 1 [6]
• Control source input 2 [7]
• Control source input 3 [8]
• Control source input 4 [9]
• Run up [10]
• Operation / bridging [11]
• Stopping [12]
• On time motor [13]
• Control command MOTOR ON
[14]
•Fan [15]
• DC braking contactor [16]
• Device - ON [18]
• Group warning [31]
• Group error [32]
• Bus error [33]
• Device error [34]
• Ready for motor on [38]
164 97 Output 2 - Action (refer to Output 1 - Action) x
165 98 Output 3 - Action (refer to Output 1 - Action) x
166 99 Output 4 - Action
100 - 111 Reserved = 0
116 112 Breakaway time 0 ... 2 s [0 ... 200] 0.01 s
117 113 Breakaway voltage 40 ... 100 % [8 ... 20] 5 %
169 114 - 115 Maximum starting time 0 ... 1000 s [0 ... 10000] 0.1 s
170 116 - 117 Starting time 0 ... 360 s [0 ... 3600] 0.1 s
171 118 - 119 Stopping time 0 ... 360 s [0 ... 3600] 0.1 s
172 120 Start torque 10 ... 100 % [2 ... 20] 5 %
118 121 Limiting torque 20 ... 200 % [4 ... 40] 5 %
173 122 Stopping torque 10 ... 100 % [2 ... 20] 5 %
123 Reserved = 0
124 Reserved = 0
119 125 Motor thermal capacity 1 ... 100 % [1 ... 100] 1 %
126 - 129 Reserved = 0
178 130 Dynamic braking torque 20 ... 100 % [4 ... 20] 5 %
43 131 Slow speed factor - clockwise rotation 3 ... 21 [3 ... 21] 1
198 132 Slow speed factor - counter-clockwise rotation 3 ... 21 [3 ... 21] 1
ID
No
.
Byte
Bit
Meaning
Only
for
data
set
131
Value range [coding] Factor