Functions
7.10 Emergency start
SIRIUS 3RW55 soft starter
132 Manual, 08/2018, A5E35630887002A/RS-AB/002
Parameters
Note
If the control source is "Digital input", only a normally open contact may be connected to this
input. A normally closed contact would result in activation of the emergency
start in the event
of a wire break.
Parameters
Description
Emergency start
Disable
The emergency start is disabled and cannot be enabled.
Manual disable / enable
(factory setting)
The emergency start can be disabled or enabled by means of
command, PIQ bit or input action.
In the event of device faults, intrinsic device protective shutdown,
process mapping errors or stall protection, no emergency start is
possible, even if it has been enabled.