Functions
7.18 3RW5 HMI High Feature
SIRIUS 3RW55 soft starter
Manual, 08/2018, A5E35630887002A/RS-AB/002
163
Emergency start With the emergency start function the system can
continue to be operated in the case of system
faults. For more information, see Chapter
Emergency start (Page 131).
Requirement:
The output n is parameterized on control source
"PIQ-DQ x.y Output n". For more information, see
Chapter Digital outputs (Page 139).
Output 3
Test mode Test with small load The auxiliary and main circuit wiring is tested
using a small load. A direction of rotation test can
be performed by visually monitoring the motor
shaft or the load connected to it.
• Activate
• Deactivate
Parameterizing the 3RW5 HMI High Feature
Requirements
● Access protection to the 3RW5 HMI High Feature is not active or has been reset.
● You are in the "Parameters > HMI" menu.
The following parameters refer to the 3RW5 HMI High Feature.
The "Do Control After Logoff", "Messages to show" and "Operation display" menus contain
further items which you can switch to with "OK".
Activate local interface Activates the local interface of the 3RW5 HMI High Feature.
This parameter is only visible if the local interface has previously been deactivated.
Before you can connect a PC with SIRIUS Soft Starter ES (TIA Portal) to the soft
starter via the local interface, the local interface must be activated.
Deactivate local interface Deactivates the local interface of the 3RW5 HMI High Feature.
This parameter is only visible if the local interface has previously been activated
Timer Lighting Dark The display switches off after the specified time has elapsed. The parameter value
"0" deactivates the shutdown of the display.
• Factory setting: 5 min
• Setting range: 0 ... 60 min
• Increment: 1 min