Messages and diagnostics
8.4 Faults and remedial actions of the 3RW55 soft starter
SIRIUS 3RW55 soft starter
Manual, 08/2018, A5E35630887002A/RS-AB/002
179
8.4
Faults and remedial actions of the 3RW55 soft starter
Faults
Cause
Remedy
Switching element overload Switching element (switch contact, power
semiconductors) too hot.
Check the ambient conditions
associated with cooling. You may
want to consider lowering the
operating characteristics.
Check the number of switching
operations.
Acknowledgment after cooling
down
Power semiconductor defective - Check the power semiconductors L1,
L2 and L3 and replace any that are
defective.
Supply voltage missing
The mains switch or the power supply is
not plugged in correctly.
There is no power.
Check the cables and the cable
connections and replace defective
components, if necessary.
Temperature sensor overload The temperature of the motor is too high.
Check the motor and the
application that is driven by the
motor.
After triggering, the motor can only
be switched on again if the
temperature has reached the
release position of the temperature
sensor.
Temperature sensor wire break A wire has broken in the sensor cable of the
temperature sensor.
Check the sensor line and the
temperature sensor.
Temperature sensor short-circuit A short-
circuit has occurred in the sensor line
of the temperature sensor.
Therm. motor model overload
The motor feeder is overloaded.
The motor temperature has exceeded a
limit.
Check the motor and the
applications driven by the motor.
You can switch on the motor again
after the cooling-off period has
expired or after deleting the thermal
motor model.
Motor overload tripping
The motor feeder has been overloaded
The temperature rise of the motor has
exceeded a limit value.
Check the motor and the
applications driven by the motor.
You can switch on the motor again
after the cooling-off period has
expired or after deleting the thermal
motor model.
Asymmetry A limit for asymmetry has been exceeded.
Asymmetry can cause an overload. Possible
causes:
Phase failure
Fault in the motor windings
Check the motor feeder and the motor.