Mounting and dismantling
3.4 Installing / mounting / removing 3RW5 HMI High Feature
SIRIUS 3RW55 soft starter
48 Manual, 08/2018, A5E35630887002A/RS-AB/002
3.4.4
Installing the 3RW5 HMI High Feature in the control cabinet door
Requirements
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
Disassembled 3RW5 HMI High Feature
An HMI connecting cable (accessory) of suitable length
Cutout of suitable size in the control cabinet door
PZ2 screwdriver in installation with IP65 door mounting kit
Depth of the 3RW5 HMI High Feature:
Total depth: 32 mm
Recessed depth: 26 mm
Permissible wall thickness of the control cabinet door:
Without IP65 door mounting kit: 1.5 to 3.0 mm
With IP65 door mounting kit: 1.0 to 7.0 mm
Optional accessories:
IP65 door mounting kit
Procedure without IP65 door mounting kit
Place the 3RW5 HMI High Feature in the cutout of the control cabinet door . Ensure that
the 3RW5 HMI High Feature engages audibly in the 4 fixtures
.