EasyManua.ls Logo

Siemens SIRIUS 3RW55 - Page 137

Siemens SIRIUS 3RW55
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
7.12 Inputs
SIRIUS 3RW55 soft starter
Manual, 08/2018, A5E35630887002A/RS-AB/002
137
Process image input (PII)
Process data
Process image
DI 0.0
Ready (automatic)
DI 0.1 Motor On
DI 0.2
Group error
DI 0.3
Group warning
DI 0.4
Input 1
DI 0.5
Input 2
DI 0.6
Input 3
DI 0.7
Input 4
DI 1.0
Motor current Iact-bit0
DI 1.1
Motor current Iact-bit1
DI 1.2
Motor current Iact-bit2
DI 1.3
Motor current Iact-bit3
DI 1.4
Motor current Iact-bit4
DI 1.5
Motor current Iact-bit5
DI 1.6
Manual operation local
DI 1.7
Ramp operation
DI 2.0
Motor CW
DI 2.1
Motor CCW
DI 2.4
Start mode active
DI 2.5
Operation / bypass active
DI 2.6 Stop mode active
DI 2.7
Test operation active
DI 3.0
Thermal motor model overload
DI 3.1
Temperature sensor overload
DI 3.2
Switching element overload
DI 3.3
Cooling time active
DI 3.4
Device error
DI 3.5
Automatic parameterization active
AI 4 (Float32)
Measured value 1
You can find more information on
the settable measured values in
Chapter Cyclic send data
(Page 142).
AI 8 (Float32)
Measured value 2
AI 12 (Float32) Measured value 3