Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
338 Manual, 09.2018, A5E36758446-5-76
ActualUpdateState
Display name
Data type
Definition
Description
UpdateProgress UInt32 AnalogItemType Firmware update progress
(0 - 100 %)
UpdateState UInt32 AnalogItemType Status or result of the ongoing or
completed firmware update:
0: Firmware is being updated
1: The file download was exited,
the system must be restarted to
initiate the internal update process.
2: The data format of the update
file was not accepted.
3: The update file is too big.
4: The update file does not match
this device.
5: The device is in the buffer mode,
and cannot be updated at the pre-
sent time.
General
Display name
Data type
Definition
Description
ModuleMaximumChargingpo-
werSetpoint
Enumeration MultiStateDiscrete-
Type
Maximum permissible charging
power (0 W = off, 60 W = low,
120 W = high)
ModuleBatteryTestIntervalSetpoint Byte MultiStateDiscrete-
Type
Interval in which the automatic
battery test is executed (0 = never,
1, …, 24 = every 1, …,24 hours)
ModuleBufferTimerEnableSetpoint Boolean PropertyType The buffer time is activated
ModuleBufferTimerSetpoint Integer AnalogItemType Set time until the buffer timer ex-
pires in ms
Alarm
Display name
Data type
Definition
Description
Alarm_F_CommunicationToModule Boolean PropertyType Communication with the expansion
module is faulty. All outputs on the
expansion module have been
switched off.
Alarm_F_General
Boolean
PropertyType
General error
Alarm_F_IncompatibleModuleDe-
tected
Boolean PropertyType The module has a module type that
is incompatible with the configura-
tion. The module cannot be com-
missioned.
Alarm_F_ModuleDefect Boolean PropertyType A hardware failure has occurred.
All outputs of the power supply
system have been switched off.
Alarm_F_ModuleParameters
Corrupt
Boolean PropertyType Stored module configuration is
corrupt. The module cannot start
up correctly.