Medium settings
Path settings
No
Process parameters
Sensor settings (4)
Yes
Medium settings
Custom
Text Options/Description
Medium settings Select "Yes" to configure the medium.
Medium settings Select the process medium.
Process parameters Set the expected sound velocity (only available if custom process medium
is selected) and the process temperature, pressure, kinetic viscosity, and
density.
Note
Important!
The entry of fixed process kinematic viscosity and/or fixed process density in this menu will be
ignored for the following cases:
1. One or more analog input are enabled and assigned to either "density" and/or "kinematic
viscosity". This overrides the corresponding fixed process values.
2. The Hydrocarbon table calculation for density and/or viscosity are enabled (applies only to
the Hydrocarbon meter variant). This overrides the corresponding fixed process values.
Commissioning
6.6 Commissioning via local display
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 59