Page 164 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS A5E33329501
mmmmm
Parameters
2.8.3.3. Discrete Input State
Sets the state of the discrete input (2.8.3.2.Discrete Input Number) that will
cause the Switch Alarm to activate.
2.8.3.4. Assigned Relay
Determines which relay (if any) will be activated when the Switch Alarm
activates.
2.8.3.5. Alarm State
Read only. Used to view the current state of the Switch Alarm.
2.8.4. In-bounds Level Alarm
Reported when material level is within a user-defined range (see
2.8.4.2.High Level Value
and
2.8.4.3.Low Level Value
).
2.8.4.1. Enable
Enables/disables In-bounds Level Alarm.
2.8.4.2. High Level Value
Sets the upper level value for range within which the In-bounds Level
Alarm will activate
.
2.8.4.3. Low Level Value
Sets the lower level value for range within which the In-bounds Level Alarm
will activate.
Options
*
ON
OFF
Options
*
NO RELAY
RELAY 1
RELAY 2
RELAY 3
Options
ACTIVE
INACTIVE
Options
ENABLED
* DISABLED
Values
Range: 0.000 to 99999.000
Default: 0.000
Values
Range: 0.000 to 99999.000
Default: 0.000