33
TROUBLE MESSAGES
Trouble messages from the audio system are shown on the alphanumeric display and entered into the Trouble Log.
The operator uses the operator interface panel keys to acknowledge the trouble, silence the alarm, and reset the
trouble condition. See Section 3, Trouble Conditions for required operations.
AUDIO Walk Test
The Audio Walk Test
announces zone numbers rather than pulsing zone numbers. To report a zone, the system
announces the words TESTING ZONE along with the digits of the zone number associated with that point. For
example, if zone 97 were being tested, the system would announce TESTING ZONE NINE SEVEN. (See Section
10 for Walk Test
Procedures.)
Walk Test
TROUBLE AUDIBLE
If a trouble is detected on a zone during the Walk Test
, the system will first announce the message TESTING
ZONE (along with the digits of the zone being tested), and then say TROUBLE. For example, if an open circuit
trouble is detected on zone 97, the system announces TESTING ZONE NINE SEVEN, TROUBLE.
Testing of signal circuit supervision and system troubles (e.g., earth ground trouble) was added in Version 3.01 of
the 4100 system software.
SINGLE CHANNEL AUDIO OPERATIONS
AUDIO CONTROL LED/SWITCH MODULE
Figure 12 shows a single channel Audio Control LED/Switch Module controlling the following functions:
ALL SPEAKERS EVAC
SELECTIVE EVAC
ALL SPEAKERS TALK
LOCAL SPEAKER.
The function of each switch is explained in the following paragraphs.
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes

Related product manuals