EasyManua.ls Logo

Simplex 4100U - Printing Reports

Simplex 4100U
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-6
Dedicated Smoke Control System wiring is usually straightforward. The Smoke Control System is
the only source for commands to the fans and dampers, and therefore bypass and cut-off relays are
not needed. The following sections illustrate some examples of dedicated fan and damper control.
Damper control is a basic function of the Simplex Smoke Control System. Interconnections to
motorized dampers are shown in Figures 4-2 and 4-3.
The figure below shows dedicated motorized damper control using a 4090-9120 6-Point I/O
Module. Both relay outputs are used, one to control opening the damper and the other to control
closing it.
The wiring between the 6-Point I/O Module and the control relays is unsupervised, so the module
must be mounted within three feet of the relays/dampers in accordance with NFPA 72.
Note: The wiring to the limit switches is supervised and limited to 500 ft. (152 m).
SMOKE DAMPER
DAMPER
CLOSED
POWER
RETURN
DAMPER
OPEN
POWER
N/O
MOTOR
COMM
CLOSED POSITION
LIMIT SWITCH
OPEN POSITION
LIMIT SWITCH
N/O
COMM
POWER
SOURCE
6.8 K 1/2 W EOLR
(Per Installation Instructions, 574-876)
IDNet +
IDNet -
INPUT 1
COMM
N/O
COMM
N/O
INPUT 2
LISTED
CONTROL
RELAY
(N/O)
LISTED
CONTROL
RELAY
(N/O)
+24V
FROM
FACP
1A @ 30 VDC
or
1/4 A @ 120 VAC
0V
Figure 4-2. Dedicated Motorized Damper Control Using a 6-Point I/O Module
Continued on next page
Dedicated Smoke Control System Wiring
Overview
Dedicated
Damper Control

Table of Contents

Other manuals for Simplex 4100U

Related product manuals