5-19
Label: REPORT TBL IF SUP DAMPER 3 NOT OPEN Equation 35
COMMENTS:
INPUTS:
The ON state of:
M1-17 CDAMPER 3RD FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A272
AND NOT the ON state of:
M1-27 UTILITY MONITOR FLR 3 SUPPLY AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P262 UTILITY FL3 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 3 NOT CLOSED Equation 36
COMMENTS:
INPUTS:
NOT the ON state of:
M1-17 CDAMPER 3RD FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A273
AND NOT the ON state of:
M1-31 UTILITY MONITOR FLR 3 SUPPLY AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P262 UTILITY FL3 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 4 NOT OPEN Equation 37
COMMENTS:
INPUTS:
The ON state of:
M1-18 CDAMPER 4TH FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A274
AND NOT the ON state of:
M1-28 UTILITY MONITOR FLR 4 SUPPLY AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P263 UTILITY FL4 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 4 NOT CLOSED Equation 38
COMMENTS:
INPUTS:
NOT the ON state of:
M1-18 CDAMPER 4TH FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A275
AND NOT the ON state of:
M1-32 UTILITY MONITOR FLR 4 SUPPLY AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P263 UTILITY FL4 SUPPLY AIR DAMPER FAIL
END:
Smoke Control System Custom Control Equations, Continued
Equation 35:
Report TBL If SUP
Damper 3 Not Open
Equation 36:
Report TBL If
SUP Damper 3
Not Closed
Equation 37:
Report TBL If SUP
Damper 4 Not Open
Equation 38:
Report TBL If
SUP Damper 4
Not Closed