Like smoke dampers, fan control is a basic function of the Simplex Smoke Control System.
General principles for interconnection to a dedicated fan are shown in Figures 4-4 and 4-5.
In a dedicated fan control application, the 4090-9118 Relay IAM is used to provide inputs to a fan
to turn it ON and monitor the feedback from the controller. The wiring between the Relay IAM
and the fan is unsupervised, so the IAMs must be mounted within three feet of the controller in
accordance with NFPA 72.
LISTED
SAIL
SWITCH
N/O COMM
POWER
SOURCE
IDNet SLC
FROM FACP
LISTED
RELAY
(N/O)
SERVICE
DISCONNECT
FAN
6.8 K 1/2 W EOLR
(Per Installation Instructions 574-874)
RETURN
1A @ 30 VDC
or
1/4 A @ 120 VAC
INPUT
COMM
N/O
Figure 4-4. Dedicated Fan Control Using a Relay IAM
Continued on next page
Dedicated Smoke Control System Wiring, Continued
Dedicated
Fan Control

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485

Related product manuals