5-8
Label: SET NORMAL CONDITIONS AT RESET Equation 3
COMMENTS:
INPUTS:
The ON state of:
A21 TIMER SYSTEM RESET PULSE TIMER
OUTPUTS:
HOLD points ON pri=9,9
P290 UTILITY SET NORMAL CONDITIONS AT RESET
END:
Label: SET NORMAL CONDITIONS AT RESET Equation 4
COMMENTS:
INPUTS:
OR the UP state of:
8-65 SWITCH Ann 1 Pt 65 Graphic LED/SW Ctlr w/32
8-66 SWITCH Ann 1 Pt 66 Graphic LED/SW Ctlr w/32
8-67 SWITCH Ann 1 Pt 67 Graphic LED/SW Ctlr w/32
8-68 SWITCH Ann 1 Pt 68 Graphic LED/SW Ctlr w/32
8-69 SWITCH Ann 1 Pt 69 Graphic LED/SW Ctlr w/32
8-70 SWITCH Ann 1 Pt 70 Graphic LED/SW Ctlr w/32
8-71 SWITCH Ann 1 Pt 71 Graphic LED/SW Ctlr w/32
8-72 SWITCH Ann 1 Pt 72 Graphic LED/SW Ctlr w/32
8-73 SWITCH Ann 1 Pt 73 Graphic LED/SW Ctlr w/32
8-74 SWITCH Ann 1 Pt 74 Graphic LED/SW Ctlr w/32
8-75 SWITCH Ann 1 Pt 75 Graphic LED/SW Ctlr w/32
8-76 SWITCH Ann 1 Pt 76 Graphic LED/SW Ctlr w/32
8-77 SWITCH Ann 1 Pt 77 Graphic LED/SW Ctlr w/32
8-78 SWITCH Ann 1 Pt 78 Graphic LED/SW Ctlr w/32
8-79 SWITCH Ann 1 Pt 79 Graphic LED/SW Ctlr w/32
OR the DOWN state of:
8-65 SWITCH Ann 1 Pt 65 Graphic LED/SW Ctlr w/32
8-66 SWITCH Ann 1 Pt 66 Graphic LED/SW Ctlr w/32
8-67 SWITCH Ann 1 Pt 67 Graphic LED/SW Ctlr w/32
8-68 SWITCH Ann 1 Pt 68 Graphic LED/SW Ctlr w/32
8-69 SWITCH Ann 1 Pt 69 Graphic LED/SW Ctlr w/32
8-70 SWITCH Ann 1 Pt 70 Graphic LED/SW Ctlr w/32
8-71 SWITCH Ann 1 Pt 71 Graphic LED/SW Ctlr w/32
8-72 SWITCH Ann 1 Pt 72 Graphic LED/SW Ctlr w/32
8-73 SWITCH Ann 1 Pt 73 Graphic LED/SW Ctlr w/32
8-74 SWITCH Ann 1 Pt 74 Graphic LED/SW Ctlr w/32
8-75 SWITCH Ann 1 Pt 75 Graphic LED/SW Ctlr w/32
8-76 SWITCH Ann 1 Pt 76 Graphic LED/SW Ctlr w/32
8-77 SWITCH Ann 1 Pt 77 Graphic LED/SW Ctlr w/32
8-78 SWITCH Ann 1 Pt 78 Graphic LED/SW Ctlr w/32
8-79 SWITCH Ann 1 Pt 79 Graphic LED/SW Ctlr w/32
AND the ON state of:
P290 UTILITY SET NORMAL CONDITIONS AT RESET
OUTPUTS:
TRACK points ON pri=9,9
P256 TROUBLE FSCS SWITCHES NOT RESET
END:
Smoke Control System Custom Control Equations, Continued
Equation 3:
Set Normal
Conditions at Reset
Equation 4:
Set Normal
Conditions at Reset

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485

Related product manuals