5-21
Label: REPORT TBL IF EXH DAMPER 3 NOT OPEN Equation 43
COMMENTS:
INPUTS:
The ON state of:
M1-21 CDAMPER 3RD FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A278
AND NOT the ON state of:
M1-35 UTILITY MONITOR FLR 3 EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 3 NOT CLOSED Equation 44
COMMENTS:
INPUTS:
NOT the ON state of:
M1-21 CDAMPER 3RD FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A260
AND NOT the ON state of:
M1-39 UTILITY MONITOR FLR 3 EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 4 NOT OPEN Equation 45
COMMENTS:
INPUTS:
The ON state of:
M1-22 CDAMPER 4TH FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A279
AND NOT the ON state of:
M1-36 UTILITY MONITOR FLR 4 EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 4 NOT CLOSED Equation 46
COMMENTS:
INPUTS:
NOT the ON state of:
M1-22 CDAMPER 4TH FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A261
AND NOT the ON state of:
M1-40 UTILITY MONITOR FLR 4 EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
END:
Smoke Control System Custom Control Equations, Continued
Equation 43:
Report TBL If EXH
Damper 3 Not Open
Equation 44:
Report TBL If
EXH Damper 3
Not Closed
Equation 45:
Report TBL If EXH
Damper 4 Not Open
Equation 46:
Report TBL If
EXH Damper 4
Not Closed