SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 101
232.04 GdCurNom Utility grid nominal
current in A
0.0 A to 50.0 A 1 Sunny Island 16.0 A
0.0 A to 100.0 A 2 Sunny Island inverters
paralle
0.0 A to 150.0 A 3 Sunny Island inverters
parallel
0.0 A to 50.0 A Three-phase
232.05 GdFrqNom Utility grid nominal
frequency in Hz (expert
mode)
232.05 GdFrqMin
to
232.06 GdFrqMax
230 V / 50 Hz 50.00 Hz
220 V / 60 Hz 60.00 Hz
232.06 GdFrqMin Minimum power
frequency in Hz (expert
mode, protected by
SMA Grid Guard)
40.00 Hz to
232.04 GdFrqNom
230 V / 50 Hz 47.50 Hz
220 V / 60 Hz 59.30 Hz
232.07 GdFrqMax Maximum power
frequency in Hz (expert
mode, protected by
SMA Grid Guard)
232.05 GdFrqNom
to 70.00 Hz
230 V / 50 Hz 51.50 Hz
220 V / 60 Hz 60.50 Hz
232.08 GdVldTm Minimum observation
time for line voltage and
frequency in the
permissible range for
connection in s (expert
mode, protected by SMA
Grid Guard)
5 s to 900 s VDE-AR-N 4105
AS4777
60 s
220 V / 60 Hz 300 s
232.09 GdMod Grid interface (expert
mode)
GridCharge Charge on utility grid GridCharge
GridFeed Charge and feedback
on utility grid
232.10 GdRvPwr Permissible active power
of grid reverse power
in W (expert mode)
0 W to 5,000 W 1 Sunny Island or
single-cluster system
100 W
0 W to 20,000 W Multicluster system 100 W
232.11 GdRvTm Permissible time for grid
reverse power in s
(expert mode)
0sto 60s ‒ 5s
232.16 GdAlSns Sensitivity of the
anti-islanding detection
(expert mode, protected
by SMA Grid Guard)
Low Low Normal
Medium Medium
Normal Normal
High High
232.38 GdVtgIncProEna Voltage increase
protection (protected by
SMA Grid Guard)
Enable Enable ‒
Disable Disable
No. Name Description Value Explanation Default
value