SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 65
9.4.9 General Category (9xx)
9.5 Frequently Asked Questions
9.5.1 Questions regarding the Sunny Island
The Sunny Island does not switch off even though you have opened the load-break switch of the
BatFuse?
The Sunny Island may still be supplied from the AC side.
Switch off all AC sources and disconnect them from the Sunny Island.
The Sunny Island does not switch to silent mode?
Another function might have a higher priority than silent mode, e.g. equalization charge or full charge.
W 887 Sic4ComLoss 1 Last communication with the
Sunny Island Charger 4 was
more than 24 hours ago.
Ensure that undamaged CAT5e cables
are used for communication and that the
cables are plugged in correctly.
Ensure that the configuration of the Sunny
Island Charger with the DIL switches is
correct.
Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
W 890 BoxMeas 2 Disturbance in voltage or
current measurement at the
measurement point of the
Multicluster Box for the master.
Ensure that the control and measuring
cable between the Multicluster Box and
the corresponding Sunny Island of the
main cluster is correctly inserted. When
doing so, observe the correct sequence of
the Multicluster Box terminals to the Sunny
Island inverters (see installation manual of
the Sunny Island and the Multicluster Box
documentation).
W 891 BoxMeasSlv1 2 Disturbance in voltage or
current measurement at the
measurement point of the
Multicluster Box for slave 1.
W 892 BoxMeasSlv2 2 Disturbance in voltage or
current measurement at the
measurement point of the
Multicluster Box for slave 2.
No. Name Level Cause
W 915 Timeout 1 An error has occurred in the program run sequence.
F 952 ExtBMSTimeout 3 Time for communication with the external battery management has been
exceeded.
W 953 WrnExtBMSTmOut 1 Time for communication with the external battery management has been
exceeded.
No. Name Level Cause Corrective measures

Table of Contents