13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
120 SI60H-80H-BE-en-20 Operating Manual
13.5 Operation (500#)
13.5.1 Inverter (510#)
No. Name Description Value Explanation Default value
510.01 InvRs Trips a restart of the Sunny Island No Do not restart
Yes Restart
510.02 InvTmOpEna Time-controlled operation Disable Disable Disable
Enable Enable
510.03 InvTmOpStrDt Start date for time-controlled
operation in dd.mm.yyyy
‒‒
510.04 InvTmOpStrTm Time for the start of time-controlled
operation in hh:mm:ss
00:00:00 to
23:59:59
‒‒
510.05 InvTmOpRnDur Run time for time-controlled
operation in hh:mm:ss
00:00:00 to
99:59:00
‒‒
510.06 InvTmOpCyc Repetition cycle for time-controlled
operation
Single Once Single
Daily Daily
Weekly Weekly
510.07 CntRs Delete energy meter
The value indicates which energy
meter is to be deleted.
Inv Sunny Island
Bat Battery
Gn Generator
Gd Utility grid
All All energy
meters
Sic1 Sunny Island
Charger1
Sic2 Sunny Island
Charger2
Sic3 Sunny Island
Charger3
Sic4 Sunny Island
Charger4
SicAll All Sunny Island
Charger devices
510.08 TstClstCom Activation of communication test
between individual clusters (expert
mode)
Off Off
Transmit Enable
510.09 ClstComStt Status of communication test (expert
mode)
Wait Wait
OK Completed