13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
100 SI60H-80H-BE-en-20 Operating Manual
13.2.3 External/Backup (230#)
231# General
232# Grid Control
No. Name Description Value Explanation Default
value
231.01 PvFeedTmStr Start time for PV grid feed-in
in hh:mm:ss (expert mode)
00:00:00
to
23:59:59
‒04:00:00
231.02 PvFeedTmStp Stop time for PV grid feed-in
in hh:mm:ss (expert mode)
00:00:00
to
23:59:59
‒22:00:00
231.03 ExtLkTm Lock time after reverse
power or relay protection
in minutes (expert mode)
0min to
60 min
‒20min
231.06 ExtSrc Generator and grid
operating mode
PvOnly Only AC sources in the
stand-alone grid, no generator
in the off-grid system
‒
Gen Generator
Grid Utility grid
GenGrid Generator or utility grid
231.14 AC2NSel Terminal at which the neutral
conductor is connected to
AC2.
N The neutral conductor is
connected to terminal N.
‒
NTT The neutral conductor is
connected to terminal N
TT
.
No. Name Description Value Explanation Default
value
232.01 Country Country data set
(protected by
SMA Grid Guard)
Other Individual setting ‒
VDE-AR-4105 Code of Practice
VDE-AR-N 4105
−
AS4777 Standard AS4777
232.02 GdVtgMin Minimum line voltage
in V (expert mode,
protected by
SMA Grid Guard)
172.50 V to
210.01 InvVtgNom
230 V / 50 Hz 184.00 V
220 V / 60 Hz 194.00 V
232.03 GdVtgMax Maximum line voltage
in V (expert mode,
protected by
SMA Grid Guard)
210.01 InvVtgNom
to 264.50 V
230 V / 50 Hz 264.50 V
220V / 60Hz 242.00V