SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 99
223# Protection
224# BatSilentmode
225# Current Sensor
No. Name Description Value Default
value
223.01 BatPro1TmStr Start time of the battery protection mode level 1 in hh:mm:ss
(expert mode)
00:00:00 to
23:59:59
22:00:00
223.02 BatPro1TmStp Stop time of the battery protection mode level 1 in hh:mm:ss
(expert mode)
00:00:00 to
23:59:59
06:00:00
223.03 BatPro2TmStr Start time of the battery protection mode level 2 in hh:mm:ss
(expert mode)
00:00:00 to
23:59:59
17:00:00
223.04 BatPro2TmStp Stop time of the battery protection mode level 2 in hh:mm:ss
(expert mode)
00:00:00 to
23:59:59
09:00:00
223.05 BatPro1Soc SOC for battery protection mode level 1 in % (expert mode) 0% to 70% 20%
223.06 BatPro2Soc SOC for battery protection mode level 2 in % (expert mode) 0% to 70% 15%
223.07 BatPro3Soc SOC for battery protection mode level 3 in % (expert mode) 0% to 70% 10%
No. Name Description Value Explanation Default
value
224.01 BatSilentEna Silent mode on utility grid (expert mode) Disable Disable Disable
Enable Enable
224.02 BatSilentTmFlo Maximum time for float charge until switch to
silent mode in hours (expert mode)
1 h to 48 h 3 h
224.03 BatSilentTmMax Maximum time for standby in silent mode
until switch to float charge in hours (expert
mode)
1 h to 168 h 12 h
No. Name Description Value Explanation Default value
225.01 BatCurSnsTyp Type of battery current
sensor
None No sensor is
connected
None
60 mV 60 mV type
50 mV 50 mV type
225.02 BatCurGain60 60 mV type in
A
60 mV
0
A
60 mV
to
1,800
A
60 mV
‒100
A
60 mV
225.03 BatCurGain50 50 mV type in
A
50 mV
0
A
50 mV
to
1,800
A
50 mV
‒100
A
50 mV
225.04 BatCurAutoCal Automatic calibration of
external battery current
sensor
Start Start automatic
calibration

Table of Contents