SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 89
114# Slave2
13.1.2 Battery (120#)
No. Name Description Value Explanation
114.01 InvOpSttSlv2 Operating state of slave 2 Init (1) Initialization
Startup (2) Switch from standby to operation
Standby (3) Standby
Run (4) Operation
I-Loop (5) Current-controlled generator
operation
Error (6) Error status
114.02 InvPwrAtSlv2 Active power of slave 2 in kW ‒ ‒
114.03 InvVtgSlv2 Voltage of slave 2 in V ‒ ‒
114.04 InvCurSlv2 Current of slave 2 in A ‒ ‒
114.05 InvPwrRtSlv2 Reactive power of slave 2 in kVAr
(expert mode)
‒‒
114.06 Rly1SttSlv2 State of multifunction relay 1 in
slave 2
Off Multifunction relay is deactivated.
On Multifunction relay is activated.
114.07 Rly2SttSlv2 State of multifunction relay 2 in
slave 2
Off Multifunction relay is deactivated.
On Multifunction relay is activated.
114.09 TrfTmpSlv2 Temperature of the transformer in
slave 2 in °C (expert mode)
‒‒
114.10 HsTmpSlv2 Temperature of the heat sink in
slave 2 in °C (expert mode)
‒‒
No. Name Description Value (plain
text no.)
Explanation
120.01 BatSoc State of charge of the battery (SOC) based on the
nominal battery capacity in %
0% to 100% ‒
120.02 BatVtg Battery voltage in V ‒ ‒
120.03 BatChrgVtg Charging voltage setpoint in V ‒ ‒
120.04 AptTmRmg Remaining absorption time upon completion of
the active charging process 120.05 BatChrgOp
in hh:mm:ss
‒‒
120.05 BatChrgOp Active charging process Boost (1) Fast charge
Full (2) Full charge
Float (3;7) Float charge
Equalize (4;5) Equalization charge
Silent (6;8) Silent mode active
120.06 TotBatCur Total battery current of the cluster in A ‒ ‒
120.07 BatTmp Battery temperature in °C ‒ ‒