9 Troubleshooting SMA Solar Technology AG
50 SI60H-80H-BE-en-20 Operating Manual
9.4.3 Generator or Utility Grid Category (3xx)
No. Name Level Cause Corrective measures
W 309 RlyProtect 1 Excessive current has been
applied to the internal
transfer relay of the master.
Reduce the total power of the loads, e.g.
by staggering their use over time.
Connect the loads with very high power
directly to the generator whenever
possible or connect the utility grid. Ensure
that the generator is not overloaded.
In off-grid systems, ensure that the country
data sets of the SMA inverters are set to
stand-alone grid operation
(see the installation manuals of the SMA
inverters).
W 310 RlyProtectSlv1 1 Excessive current has been
applied to the internal
transfer relay of slave 1.
W 311 RlyProtectSlv2 1 Excessive current has been
applied to the internal
transfer relay of slave 2.
F 314 ExtVtgLoss 2 Voltage and/or frequency of
the generator or the battery
backup grid are outside of
the limiting values set.
Corrective measures for a generator:
Adjust the limiting values for frequency
and/or voltage of the generator on the
Sunny Island (see installation manual of
the Sunny Island). Observe and analyze
the measured values 134.02 ExtVtg
and 134.04 ExtFrq during operation.
Adjust the generator voltage and/or
generator frequency.
Corrective measures for a battery
backup grid:
Contact the SMA Service Line if required.
W 315 ExtVtgLo 1 Voltage at terminal AC2 of
the master is too low.
Corrective measures for a generator:
Adjust the limiting values for voltage of
the generator on the Sunny Island (see
installation manual of the Sunny Island).
Observe and analyze the measured
values 134.02 ExtVtg during operation.
If possible, adjust the generator voltage.
Corrective measures for a battery
backup grid:
Contact the SMA Service Line if required.
W 316 ExtVtgLoSlv1 1 Voltage at terminal AC2 of
slave 1 is too low.
W 317 ExtVtgLoSlv2 1 Voltage at terminal AC2 of
slave 2 is too low.
W 319 ExtVtgHi 1 Voltage at terminal AC2 of
the master is too high.
W 320 ExtVtgHiSlv1 1 Voltage at terminal AC2 of
slave 1 is too high.
W 321 ExtVtgHiSlv2 1 Voltage at terminal AC2 of
slave 2 is too high.