SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 49
W 209 BatVtgWrnHi 1 The battery voltage is too high
and has not been generated by
the Sunny Island.
Ensure that all DC sources are correctly
configured.
Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
W 210 BatVtgHiWarn 1 Battery voltage is temporarily
too high.
Ensure that all DC sources are correctly
configured.
Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
W 211 BatTmpLoWarn 1 The battery temperature is too
low.
Ensure that the battery room is sufficiently
warm.
W 212 BatTmpHiWarn 1 The battery temperature is too
high.
Wait for the battery to cool down. Tip:
Protect the battery against temperatures
above 25°C. This helps prevent
premature aging of the battery.
F 213 BatVtgLow 3 Battery voltage is too low.
Charge the battery in emergency charge
operation or using an external battery
charger (see Section9.6 "Charging the
Battery after Automatic Shutdown in
Off-Grid Systems", page69).
Ensure that DC loads are shed via a
load-shedding contactor when the
battery state of charge is low.
W 220 BatSOH70Warn 1 Available battery capacity is
below 70%.
Verify the plausibility of the error message
and replace the battery if necessary.
F 221 InvalidBatType 4 External battery management
detected although no external
energy management is
configured.
Start QCG and configure a new system
with external energy management (e.g.
system with lithium-ion battery).
W 222 CheckBat 1 The 20% recalibration resulted
in a jump of more than 10%.
Check the battery.