EasyManua.ls Logo

SMA SUNNY ISLAND 6.0H - Slfcsmpbackup (#260)

SMA SUNNY ISLAND 6.0H
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
114 SI60H-80H-BE-en-20 Operating Manual
13.2.6 SlfCsmpBackup (#260)
261# General
262# BatUsage
No. Name Description Value
(plain text
no.)
Explanation Default
value
261.01 SlfCsmpIncEna Increased self-consumption Disable Disable
Enable Enable
261.02 SlfCsmpPosSel System location (expert mode) North Northern hemisphere
South Southern hemisphere
261.03 Saisonenable Automatic alignment of the
battery depth of discharge
(expert mode)
In seasons with fewer hours of
sunlight the battery will undergo
deep electric discharges less.
No Disable Yes
Yes Enable
No. Name Description Value
(plain text
no.)
Explanation Default
value
262.01 ProtResSOC Range for protection in the event
of deep discharge as a
percentage of the battery
capacity (expert mode)
10% to 20% Lead-acid batteries 10%
3% to 20% Lithium-ion batteries 3%
262.02 BatResSOC Range for protection against
deep discharge as a percentage
of the battery capacity (expert
mode)
2% to 50% Lithium-ion battery,
self-consumption only
2%
Lithium-ion battery
battery backup system
10%
Lead-acid battery,
self-consumption only
30%
Lead-acid battery,
battery backup system
5%
262.03 BUResSOC Range for the battery backup
function on the longest day of
the year as a percentage of the
battery capacity (expert mode)
0% to 100% 0%
262.04 PVResSOC Range for maintaining the state
of charge of the battery as a
percentage of the nominal
capacity (expert mode)
4% to 20% 5%
262.05 MinSlfCsmpSOC Range for increased
self-consumption on the shortest
day of the year as a percentage
of the battery capacity (expert
mode)
0% to 100% Lithium-ion battery 70%
Lead-acid battery 35%

Table of Contents

Other manuals for SMA SUNNY ISLAND 6.0H