EasyManua.ls Logo

SMA SUNNY ISLAND 6.0H - Page 113

SMA SUNNY ISLAND 6.0H
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 113
250.24 ClstMod Cluster type (adjustable in
QCG)
SingleClst Single cluster
MainClst Main cluster
ExtnClst Extension cluster
250.26 MtrDatSel Readout device for energy
meters
MtrBox Meter Box for Sunny Backup
HomeMngr Sunny Home Manager
250.29 ChrgCtlOp Types of energy sources in
the system (expert mode)
Auto AC sources and DC charge
controllers
Auto
NoFrq DC charge controllers only
The DC charge controllers
are not
Sunny Island Charger
devices and there are no AC
sources in the system.
SMA Sunny Island Charger
devices only
No AC sources in the system.
250.31 RnMod Run Mode
Behavior under fault
conditions
RunAlways In the event of a slave device
error, the cluster remains in
operation
RunAlways
StopAlways In the event of a device error,
the cluster stops operation
250.32 ChLstSel Selection of short or normal
channel list (expert mode)
The length must be
compatible with the
communication device.
Short Short Normal
Normal Normal
250.33 UpdMode Type of firmware update Manual Update must be confirmed
on the Sunny Remote
Control.
Manual
Auto Update will be performed
automatically at the set time
250.34 UpdAutoTime.
Never Deactivation of all updates
250.34 UpdAutoTime Point in time for performing
the automatic firmware
update in hh:mm:ss
00:00:00 to
23:59:59
05:00:00
No. Name Description Value Explanation Default
value

Table of Contents

Other manuals for SMA SUNNY ISLAND 6.0H

Related product manuals