SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 55
9.4.5 Utility Grid Category (5xx)
9.4.6 Relay Category (6xx)
9.4.7 System Category (7xx)
No. Name Level Cause Corrective measures
W 505 GdCurNomExceed 1 The feed-in current of the master is greater
than 232.04 GdCurNom.
Contact the SMA Service
Line if required.
W 506 GdCurNomExcSlv1 1 The feed-in current of slave 1 is greater than
232.04 GdCurNom.
W 507 GdCurNomExcSlv2 1 The feed-in current of slave 2 is greater than
232.04 GdCurNom.
No. Name Level Cause Corrective measures
F 605 TransfNotOpn 4 Internal transfer relay in the
master does not open.
A bypass switch may have bridged the internal
transfer relay.
Ensure that the bypass switch is in the
position for operation with the Sunny
Island.
Ensure that the terminals AC1 and AC2
are not bridged.
W 606 TransfNotOpnSL1 1 Internal transfer relay in
slave 1 does not open.
W 607 TransfNotOpnSL2 1 Internal transfer relay in
slave 2 does not open.
No. Name Level Cause Corrective measures
F 702 RsDsp 5 Signal processor has performed a
reset.
Contact the SMA Service Line.
F 703 TimeOut 2 Time for performing a particular task
has been exceeded.
Contact the SMA Service Line.
F 704 Calib 4 The system has not calibrated. Contact the SMA Service Line.
W 705 TimeOut 1 The watchdog of the signal processor
of the master has tripped.
Contact the SMA Service Line if
required.
F 706 TimeOut 4 The watchdog of the signal processor
of the master has tripped several
times.
Contact the SMA Service Line.
W 707 TimeOutSlv1 1 The watchdog of the signal processor
of slave 1 has tripped several times.
W 708 TimeOutSlv2 1 The watchdog of the signal processor
of slave 2 has tripped several times.
F 710 AutoStrCnt 4 Autostart meter has expired several
times in succession.
Read off the pending and logged
warnings and errors and eliminate
the causes.
Ensure that the parameter 250.01
AutoStr is set to 3.
W 713 TimeOut 1 The watchdog of the operation
control unit has tripped.
Contact the SMA Service Line if
required.