9 Troubleshooting SMA Solar Technology AG
56 SI60H-80H-BE-en-20 Operating Manual
F 716 VBATMIN 2 The measured battery voltage of the
master is below the permissible
measurement range.
Disconnect the DC loads and
charge the battery.
The usable battery capacity may be too
small, e.g. due to aging. If a load with
high power connects, the battery
voltage collapses.
If DC loads are installed in the
system, install load shedding for
DC loads.
Ensure that all battery cells are
functional.
W 717 VBATMINSL1 1 The measured battery voltage of
slave 1 is below the permissible
measurement range.
W 718 VBATMINSL2 1 The measured battery voltage of
slave 2 is below the permissible
measurement range.
F 720 InvTmpSns 4 The temperature sensor on the
transformer of the master is defective.
Contact the SMA Service Line.
F 721 InvTmpSns 4 The temperature sensor on the heat
sink of the master is defective.
Contact the SMA Service Line.
W 722 BatTmpSnsShort 1 Short circuit of the battery
temperature sensor
Ensure that the battery temperature
sensor is correctly connected (see
installation manual of the
Sunny Island).
Contact the SMA Service Line.
W 723 BatTmpSnsOpn 1 Cable break in battery temperature
sensor
W 724 AutoStrCntSlv1 1 Maximum number of autostarts for
slave 1 has been reached.
Read off the pending and logged
warnings and errors and eliminate
the causes.
Ensure that the parameter 250.01
AutoStr is set to 3.
W 725 AutoStrCntSlv2 1 The maximum number of autostarts
for slave 2 has been reached.
F 731 ClstConfig 4 Configuration of the cluster is
incorrect.
Change the addresses of the
slaves in the cluster (see
Section9.7, page71)
F 732 ClstAdress 4 Error in the address assignment of the
Sunny Island in the cluster.
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
Ensure that the communication bus
is equipped with a terminator at
both ends.
Reset the address of the Sunny
Island inverters in the cluster (see
Section 9.7, page71).