SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 57
F 733 MstrLoss 4 Communication to the master is
interrupted.
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
Ensure that the communication bus
is equipped with a terminator at
both ends.
W 734 Slv1Loss 1 Communication from the master to
slave 1 is interrupted.
W 735 Slv2Loss 1 Communication from the master to
slave 2 is interrupted.
W 738 GnSynLoss 1 Synchronization with the generator or
battery backup grid not successful.
Ensure that the generator can be
started. It may be that the fuel level
is too low.
Ensure that a constant and stable
voltage is present at terminal AC2.
Ensure that the limiting values for
the voltage of the external energy
sources are correctly configured.
F 739 SPICom 3 Internal device communication of the
master is disturbed.
Contact the SMA Service Line.
W 740 SPIComSlv1 1 Internal device communication of
slave 1 is disturbed.
W 741 SPIComSlv2 1 Internal device communication of
slave 2 is disturbed.
F 743 CANCom 3 Internal device CAN communication
of the master is disturbed.
Ensure that the terminators in the
communication bus are attached.
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
Contact the SMA Service Line.
W 744 CANComSlv1 1 Internal device CAN communication
of slave 1 is disturbed.
W 745 CANComSlv2 1 Internal device CAN communication
of slave 2 is disturbed.
W 747 InvTmpSnsSlv1 1 Temperature sensor on the
transformer of slave 1 is defective.
Contact the SMA Service Line.
W 748 InvTmpSnsSlv2 1 Temperature sensor on the
transformer of slave 2 is defective.
W 750 InvTmpSnsSlv1 1 Temperature sensor on the heat sink
of slave 1 is defective.
Contact the SMA Service Line.
W 751 InvTmpSnsSlv2 1 Temperature sensor on the heat sink
of slave 2 is defective.
W 753 DateInvalid 1 System time is invalid. Select the parameter 250.02 Dt
and set the date. Select the
parameter 250.03 Tm and set the
time.
No. Name Level Cause Corrective measures