9 Troubleshooting SMA Solar Technology AG
58 SI60H-80H-BE-en-20 Operating Manual
F 754 BoxCom 2 Communication with Multicluster Box
is interrupted.
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
Ensure that the communication bus
is equipped with a terminator at
both ends.
W 755 LoBatMod1 1 Battery protection mode protects the
battery. Level 1 is active.
Disconnect the loads, start the
generator, start the Sunny Island
and charge the battery.
W 756 LoBatMod2 1 Battery protection mode protects the
battery. Level 2 is active.
W 757 LoBatMod3 1 Battery protection mode protects the
battery. Level 3 is active.
F 758 McNoVtg 2 Voltage of the main cluster cannot be
measured at the master.
Ensure that all circuit breakers of
the Sunny Island inverters in the
Multicluster Box are closed.
Ensure that the cabling at terminal
AC1 is correctly installed.
W 759 McNoVtgSv1 1 Voltage of the main cluster cannot be
measured at slave 1.
W 760 McNoVtgSlv2 1 Voltage of the main cluster cannot be
measured at slave 2.
F 781 SlvError 4 Error at a slave in the main cluster
causing system shutdown.
Read off the pending and logged
warnings and errors and eliminate
the causes.
F 782 AIVtgMonFail 4 Monitoring of the utility grid has
failed.
Contact the SMA Service Line.
F 783 CANCom 2 Synchronization in the cluster is
interrupted at the master.
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
Ensure that the communication bus
is equipped with a terminator at
both ends.
W 784 CANComSlv1 1 Synchronization in the cluster is
interrupted at slave 1.
W 785 CANComSlv2 1 Synchronization in the cluster is
interrupted at slave 2.
F 787 VcoreFail 3 Internal device voltage in the master
is outside the tolerance limits.
Contact the SMA Service Line.
F 788 VcoreFailSlv1 3 Internal device voltage in slave 1 is
outside the tolerance limits.
F 789 VcoreFailSlv2 3 Internal device voltage in slave 2 is
outside the tolerance limits.
W 791 RsDspSlv1 1 Signal processor has performed a
reset.
Contact the SMA Service Line.
W792 RsDspSlv2 1