SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 41
Treatment of Pending Errors upon Activation
During the activation procedure, all pending errors are acknowledged without the error being logged in the list 420#
Error history. Errors which are still pending are entered again after activation. Errors which were detected by the Sunny
Island before activation and are no longer detected after activation are shown in the list 420# Error history.
Autostart
The autostart function allows automatic restarts in the event of malfunctions. If the autostart function fails in the event of a
malfunction, the Sunny Island attempts to carry out the next autostart immediately. The number of autostarts is restricted.
If the Sunny Island is in operation without malfunctions for ten minutes, it resets the autostart counter.
When the maximum number of autostarts has been reached, the Sunny Island reacts as follows:
The Sunny Island waits ten minutes.
The autostart counter is reset.
The Sunny Island attempts to perform an autostart.
When the maximum number of autostarts has been reached, the Sunny Island waits again for ten minutes.
9.2 Acknowledging Errors
If a malfunction or failure occurs, the Sunny Island switches to standby mode. Once you have remedied the cause of the
malfunction, you can enable a restart of the Sunny Island by acknowledging the error.
Procedure:
1. Eliminate the cause.
2. Press the button on the Sunny Remote Control. This acknowledges the error.
3. Start the system (see Section4.2, page17).
9.3 Logged Events
9.3.1 Sunny Island Category (1xx)
4 Failure Failure Device failure, the Sunny Island switches off. Troubleshooting,
acknowledgment of the error and manual restart necessary.
5 Device defect Defect The Sunny Island is defective and switches itself off. The Sunny Island must
be replaced.
No. Name Description
E101 Standby Waiting mode
E102 Startup Startup process
E103 Run Operation
E104 RunExtGn Operation with a generator
E105 RunExtGd Operation on the utility grid
E106 RunGdFeed Feed-in grid operation
E108 Silent Silent mode
E110 ErrShutdown Shutdown due to error