SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 51
W 323 ExtFrqLo 1 Frequency at terminal AC2
of the master is too low.
Corrective measures for a generator:
The generator may be overloaded.
Reduce the total power of the loads by
staggering their use over time.
Adjust the limiting values for generator
frequency on the Sunny Island (see
installation manual of the Sunny Island).
Observe and analyze the measured
values 134.04 ExtFrq during operation.
Adjust the frequency of the external
energy source.
Corrective measures for a utility grid:
Contact the SMA Service Line if required.
W 324 ExtFrqLoSlv1 1 Frequency at terminal AC2
of slave 1 is too low.
W 325 ExtFrqLoSlv2 1 Frequency at terminal AC2
of slave 2 is too low.
W 327 ExtFrqHi 1 Frequency at terminal AC2
of the master is too high.
W 328 ExtFrqHiSlv1 1 Frequency at terminal AC2
of slave 1 is too high.
W 329 ExtFrqHiSlv2 1 Frequency at terminal AC2
of slave 2 is too high.
W 331 AntiIsl 1 Undesired stand-alone grid
is present at terminal AC2 of
the master.
Ensure that the insulated wires at terminal
AC2 are securely connected and that the
conductors in the terminals are free of
insulation.
Corrective measures for a generator:
This may be caused by a contactor between
the generator and the Sunny Island.
Implement control of the contactor via a
Sunny Island multifunction relay. Set the
parameter of the multifunction relay, e.g.
241.01 Rly1Op, to AutoGn.
Set the parameter 234.20 GdAiSns to a
lower sensitivity.
Corrective measures for a utility grid:
Contact the SMA Service Line.
W 332 AntiIslSlv1 1 Undesired stand-alone grid
is present at terminal AC2 of
slave 1.
W 333 AntiIslSlv2 1 Undesired stand-alone grid
is present at terminal AC2 of
slave 2.
W 335 ExtVtgRdtErr 1 Voltage at terminal AC2 of
the master is outside the
configured limiting values
(redundant measurement).
Corrective measures for a generator:
Adjust the limiting values for voltage of
the generator on the Sunny Island (see
installation manual of the Sunny Island).
Observe and analyze the measured
values 134.02 ExtVtg during operation.
If possible, adjust the generator voltage.
Corrective measures for a utility grid:
Contact the SMA Service Line if required.
W 336 ExtVtgRdtErrSlv1 1 The voltage at terminal AC2
of slave 1 is outside the
configured limiting values
(redundant measurement).
W 337 ExtVtgRdtErrSlv2 1 The voltage at terminal AC2
of slave 2 is outside the
configured limiting values
(redundant measurement).
No. Name Level Cause Corrective measures