13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
118 SI60H-80H-BE-en-20 Operating Manual
320.11 FulChrgCnt Full charge counter
320.12 BatCurOfsErr Estimated offset error of battery current in A (expert mode)
320.13 OcvPointCnt Counter for open-circuit voltage points (expert mode)
320.15 AhCntFul Ampere-hour meter for battery discharging since the last full charge in
Ah
⁄
100 Ah
320.16 AhCntEqu Ampere-hour meter for battery discharging since the last equalization charge in
Ah
⁄
100 Ah
320.17 BatVtgPk Maximum battery voltage reached since the last start in V
320.18 BatCurPkIn Maximum battery current reached since the last start in charge direction in A
320.19 BatCurPkOut Maximum battery current reached since the last start in discharge direction in A
320.20 SocHgm100 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
100% to and including 90%, based on time in % (expert mode)
320.21 SocHgm090 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
90% to and including 80%, based on time in % (expert mode)
320.22 SocHgm080 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
80% to and including 70%, based on time in % (expert mode)
320.23 SocHgm070 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
70% to and including 60%, based on time in % (expert mode)
320.24 SocHgm060 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
60% to and including 50%, based on time in % (expert mode)
320.25 SocHgm050 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
50% to and including 40%, based on time in % (expert mode)
320.26 SocHgm040 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
40% to and including 30%, based on time in % (expert mode)
320.27 SocHgm030 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
30% to and including 20%, based on time in % (expert mode)
320.28 SocHgm020 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
20% to and including 10%, based on time in % (expert mode)
320.29 SocHgm010 Percentage frequency distribution of state of charge (SOC) when SOC is in the range of
10 % to and including 0 %, based on time in % (expert mode)
320.30 SocHgm000 Frequency distribution of SOC in relation to time, when SOC is equal to 0% in % (expert
mode)
320.31 SocVtgCal Recalibration of SOC based on open-circuit voltage only in % (expert mode)
320.32 ErrSocVtgCal Estimated error of the voltage-calibrated state of charge in % (expert mode)
320.33 SocChrgCal Recalibration of SOC based on full charge only in % (expert mode)
320.34 ErrSocChrgCal Estimated error of the full-charge-calibrated state of charge in % (expert mode)
320.35 OcvGra Gradient of the open-circuit voltage characteristic curve in
Ah
⁄
V
(expert mode)
320.36 OcvMax Maximum open-circuit voltage in V (expert mode)
No. Name Description