SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 53
F 365 VAcExtPhsFail 3 The line conductors of the
measured AC voltage at
terminals VExt and AC2 do
not match.
Ensure that the neutral conductor and line
conductor are correctly connected to the
terminal ExtVtg.
Ensure that the neutral conductor and line
conductor are correctly connected to
terminal AC2.
Ensure that the terminals ExtVtg and
AC2 are connected to the same line
conductor.
F 366 HotAcBus 3 When the tie switch is open,
AC voltage from an
unknown source is present at
terminal AC2.
Ensure that the triggering of the tie switch
is correct.
Ensure that the tie switch is correctly
wired.
F 367 ExtCtcNotOpen 3 Tie switch does not open.
Ensure that the triggering of the tie switch
is correct.
Ensure that the tie switch is correctly
wired.
Ensure that the feedback contact is
correctly connected.
F 368 NRelNotOpen 3 Neutral conductor relay of
the master does not open.
Contact the SMA Service Line.
W 369 NRelNotOpenSlv1 1 Neutral conductor relay of
slave 1 does not open.
W 370 NRelNotOpenSlv2 1 Neutral conductor relay of
slave 2 does not open.
W 372 VtgFrqRatio 1 Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
the master.
Contact the SMA Service Line if required.
W 373 VtgFrqRatioSlv1 1 Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
slave 1.
W 374 VtgFrqRatioSlv2 1 Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
slave 2.