SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 61
W 847 ComHMFaill 1 Faulty communication
between the Sunny Island and
Sunny Home Manager.
Ensure that the data cables are correctly
installed.
Ensure that the parameter
250.06 ComBaud is set to 115k Bd.
W 851 Sic1BatShort 1 Connection of the battery to
the Sunny Island Charger 1 is
reverse poled or there is a
short circuit.
Ensure that the battery is correctly
connected to the DC terminal of the Sunny
Island Charger.
Disconnect the PV array from the Sunny
Island Charger and restart the system.
This will ensure that the PV array is not
short-circuited.
W 852 Sic1BatVtgHi 1 Battery voltage at the Sunny
Island Charger 1 is too high.
Ensure that the configuration of the Sunny
Island Charger with the DIL switches is
correct.
Ensure that all DC sources and DC loads
are correctly configured and connected.
Reset the system. For this, switch off the
system, wait ten minutes and restart.
W 853 Sic1PvVtgHi 1 PV voltage at the Sunny Island
Charger 1 is too high.
Contact the SMA Service Line if required.
W 854 Sic1PvVtgLo 1 No PV voltage at the Sunny
Island Charger 1 or there is a
short circuit.
Contact the SMA Service Line if required.
W 855 Sic1TmpLo 1 Sunny Island Charger 1
reports a battery
undertemperature.
Set the Sunny Island Charger to the
operating mode "SMA operation" (see
installation manual of the
Sunny Island Charger).
W 856 Sic1TmpHI 1 Sunny Island Charger 1
reports a battery
overtemperature.
Set the Sunny Island Charger to the
operating mode "SMA operation" (see
installation manual of the Sunny Island
Charger).
No. Name Level Cause Corrective measures