SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 63
W 867 Sic2ComLoss 1 Last communication with the
Sunny Island Charger 2 was
more than 24 hours ago.
Ensure that undamaged CAT5e cables
are used for communication and that the
cables are plugged in correctly.
Ensure that the configuration of the Sunny
Island Charger with the DIL switches is
correct.
Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
W 871 Sic2BatShort 1 Connection of the battery to
the Sunny Island Charger 2 is
reverse poled or there is a
short circuit.
Ensure that the battery is correctly
connected to the DC terminal of the Sunny
Island Charger.
Disconnect the PV array from the Sunny
Island Charger and restart the system.
This will ensure that the PV array is not
short-circuited.
W 872 Sic3BatVtgHi 1 Battery voltage at the Sunny
Island Charger 3 is too high.
Ensure that the configuration of the Sunny
Island Charger with the DIL switches is
correct.
Ensure that all DC sources and DC loads
are correctly configured and connected.
Reset the system. For this, switch off the
system, wait ten minutes and restart.
W 873 Sic3PvVtgHi 1 PV voltage at the Sunny Island
Charger 3 is too high.
Contact the SMA Service Line if required.
W 874 Sic3PvVtgLo 1 No PV voltage at the Sunny
Island Charger 3 or there is a
short circuit.
Contact the SMA Service Line if required.
W 875 Sic3TmpLo 1 Sunny Island Charger 3
reports a battery
undertemperature.
Set the Sunny Island Charger to the
operating mode "SMA operation" (see
installation manual of the Sunny Island
Charger).
W 876 Sic3TmpHI 1 Sunny Island Charger 3
reports a battery
overtemperature.
Set the Sunny Island Charger to the
operating mode "SMA operation" (see
installation manual of the Sunny Island
Charger).
No. Name Level Cause Corrective measures

Table of Contents