SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 91
133# Gen State
134# Device
No. Name Description Value (plain
text no.)
Explanation
133.01 GnDmdSrc Source of generator request None (1) No request
Bat (2) State-of-charge-dependent request
Lod (3) Load-dependent request
Tim (4) Time-controlled request
Run1h (5) Requested for 1 hour
Start (6) Manually started
ExtSrcReq (7) External generator request
133.02 GnStt Status of the generator
management
Off (1) Deactivated generator operation
Init (2) Detecting generator
Ready (3) Waiting for request (ready)
Warm (4) Warming up
Connect (5) Connecting
Run (6) Operation
Retry (7) Restarting
Disconnect (8) Disconnecting
Cool (9) Cooling down
Lock (10) Locked after operation
Fail (11) Failure
FailLock (12) Locked after error
Reinit (13) Re-detection of the generator
133.03 GnRmgTm Remaining minimum run time of the
generator in hh:mm:ss
‒‒
133.04 GnRnStt Status of generator feedback
(expert mode)
Off (1) Off
On (2) On
No. Name Description
134.01 ExtPwrAt Active power of external energy source in kW
134.02 ExtVtg Voltage of external energy source in V
134.03 ExtCur Current of external energy source in A
134.04 ExtFrq Frequency of external energy source in Hz
134.05 ExtPwrRt Reactive power of external energy source in kVAr (expert mode)
134.07 ExtLkRmgTm Minimum stop time in hh:mm:ss