13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
96 SI60H-80H-BE-en-20 Operating Manual
163# State
No. Name Description Value Explanation
163.01 BatMntStt Status of the full charge or
equalization charge
If full charge or equalization
charge with PV energy has not
ended after 24 hours, 163.01
BatMntStt automatically
switches to On.
On Full charge or equalization
charge active, energy is drawn
from the utility grid
Wait If sufficient PV energy is available,
full charge or equalization charge
active
Off No full charge or equalization
charge active
163.02 SlfCsmpSOCArea Current range of the state of
charge of the battery
In systems for increased
self-consumption and in
backup systems, this
parameter shows in which
range the state of charge of
the battery is currently in.
SlfCsmpSOC Range for the increased
self-consumption
PVResSOC Range for maintaining the state of
charge of the battery
BUResSOC Range for battery backup function
BatResSOC Range for protection against deep
discharge
ProtResSOC Range for protection in the event
of deep discharge