The electric 
actuator does 
not move at all. 
Check if you can hear the sound 
of lock release when the manual 
lock switch is turned on and off. 
If there is no sound of lock release from 
the electric actuator with lock, the lock 
may be broken.  If the trouble 
continues, please contact SMC. 
Check that the PLC connected to 
the controller operates correctly. 
Check the operation by test run using 
the controller setting kit, etc. 
If the electric actuator is operated, a 
signal output from the PLC is suspected. 
Take appropriate measures by referring 
to the Operation Manual for the 
controller. 
→ 6.4 Parallel I/O Wiring Example 
Inappropriate 
specifications 
Check that the combination of 
the electric actuator and 
controller is correct? 
Check if the product number of the used 
the electric actuator matches with the 
electric actuator which is applicable to 
the controller. 
→ 3. Product Specifications 
If it is not energized, the servo 
will be OFF and does not 
operate. Check if a voltage of 
24 VDC is applied to the EMG 
terminal. 
Apply 24 VDC to the EMG terminal. 
Is the wiring connected 
correctly? 
Check if the wiring is connected 
correctly or if there is broken wire or 
short-circuit by referring to this 
Operation Manual. Correct the wiring 
and check that the input/output of each 
signal is correct. 
Separate the power supply for the 
CN1controller and the CN5 I/O signal 
power supply. 
→ 4. External Wiring Diagram 
→ 6.4 Parallel I/O Wiring Example 
Counter- 
measures   
against noise 
Check that the Grounding is 
connected correctly? 
Are power cables for other 
equipment and controller cables 
bundled together? 
Connect to Ground correctly. 
Avoid bundling the cables with power 
cables of other equipment. 
Take appropriate measures by referring 
to the Operation Manual for the controller. 
→ 3.4 How to install 
Check that the parameter values 
are correct. 
Check the combination of the electric 
actuator and controller. Modify the 
parameters accordingly and check the 
operation. 
→ 7. Setting Data Entry 
Check if there has been any 
temporary voltage drop in the 
power supply. 
(If there is a temporary voltage 
drop in the power supply, the 
EMG terminal of CN1 power 
connector will turn OFF so the 
electric actuator will stop. 
However, this stop will be 
released when the voltage 
recovers.) 
There is a possibility of a momentary 
voltage drop because the capacity of the 
power supply is insufficient, or the 
power supply has inrush current 
restraining specification. 
→ 3. Product Specifications